PMU : PMU allocation for IEEE 14 network without considering zero injection nodes

Reference

  • Alireza Soroudi, Power System Optimization Modelling in GAMS, Model PMU (Gcode8.1) in chapter Power System Observability, 2017

Category : GAMS PSOPT library


Mainfile : PMU.gms

$title PMU allocation for IEEE 14 network without considering zero injection nodes

$onText
For more details please refer to Chapter 8 (Gcode8.1), of the following book:
Soroudi, Alireza. Power System Optimization Modeling in GAMS. Springer, 2017.
--------------------------------------------------------------------------------
Model type: MIP
--------------------------------------------------------------------------------
Contributed by
Dr. Alireza Soroudi
IEEE Senior Member
email: alireza.soroudi@gmail.com
We do request that publications derived from the use of the developed GAMS code
explicitly acknowledge that fact by citing
Soroudi, Alireza. Power System Optimization Modeling in GAMS. Springer, 2017.
DOI: doi.org/10.1007/978-3-319-62350-4
$offText

Set bus / 1*14 /;
Alias (bus,node);

Set conex 'Bus connectivity matrix'
/
   1.2
   1.5
   2.3
   2.4
   2.5
   3.4
   4.5
   4.7
   4.9
   5.6
   6.11
   6.12
   6.13
   7.8
   7.9
   9.10
   9.14
   10.11
   12.13
   13.14
/;
conex(bus,node)$(conex(node,bus)) = 1;

Variable OF;
Binary Variable PMU(bus);
Equation const1, const2;
**********************************************************************

const1..      OF =e= sum(bus, PMU(bus));
const2(bus).. PMU(bus) + sum(node$conex(bus,node), PMU(node)) =g= 1;

option optCr = 0, profile = 1;

Model placement / const1, const2 /;
solve placement minimizing OF using mip;
display pmu.l;